SMOKE AND CFD VISUALIZATION OF THE FLOW AFTER AN EMC SCREEN IN A SUBRACK MODEL - Archive ouverte HAL Accéder directement au contenu
Communication Dans Un Congrès Année : 2005

SMOKE AND CFD VISUALIZATION OF THE FLOW AFTER AN EMC SCREEN IN A SUBRACK MODEL

Résumé

An experimental parametric study was performed in order to study the flow pattern inside a radio base station subrack model. The parameters that were analysed are the velocity, the EMC screen porosity and the subrack geometry. The technique used to visualize the flow pattern is the smoke-wire technique. The objective is not only to gain insight about the influence of those parameters in the flow pattern of the subrack but also to validate the flow pattern predictions of a detailed CFD model. A further objective is to show the importance of using an accurate CFD model in order to visualize the flow pattern in a situation in which there is a 90 degree turn followed by a perforated plate. The fact that the airflow impinges on the screen in an inclined way means that when the flow collides with the interior face of the hole, it suffers a sudden change in direction, even if the perforated plate is very thin. This change in direction is very important in order to get the right flow pattern after the screen.
Fichier principal
Vignette du fichier
therm05212.pdf (851.03 Ko) Télécharger le fichier
Origine : Fichiers produits par l'(les) auteur(s)
Loading...

Dates et versions

hal-00189475 , version 1 (21-11-2007)

Identifiants

  • HAL Id : hal-00189475 , version 1

Citer

R. Antón, M. Castiella, H. Jonsson, B. Moshfegh. SMOKE AND CFD VISUALIZATION OF THE FLOW AFTER AN EMC SCREEN IN A SUBRACK MODEL. THERMINIC 2005, Sep 2005, Belgirate, Lago Maggiore, Italy. pp.212-219. ⟨hal-00189475⟩

Collections

THERMINIC
72 Consultations
79 Téléchargements

Partager

Gmail Facebook X LinkedIn More